Operating Instructions
for the system user
Vitotronic 050
Type HK3W and HK3S
Weather-compensated, digital heating circuit control units
VITOTRONIC 050
Vitotronic 050, Type HK3W
Vitotronic 050, Type HK3S
5592 395 GB
4/2001
File in service document ring binder
Related Manuals for Viessmann VIVOTRONIC 050 HK3W
Summary of Contents for Viessmann VIVOTRONIC 050 HK3W
-
Page 1
Operating Instructions for the system user Vitotronic 050 Type HK3W and HK3S Weather-compensated, digital heating circuit control units VITOTRONIC 050 Vitotronic 050, Type HK3W Vitotronic 050, Type HK3S 5592 395 GB 4/2001 File in service document ring binder… -
Page 2: For Your Safety
Introductory information For your safety Please follow these safety instructions closely to avoid the risk of injury to persons and damage to property. If you smell gas Work on the equipment Boiler room conditions H Don’t smoke! Don’t use naked Installation, initial start-up, mainte H Do not use a room in which the air flames or cause sparks (e.g.
-
Page 3: Table Of Contents
Index Page Useful tips Introductory information For your safety ………………..Instructions in brief Ready for operation The main controls…
-
Page 4: Ready For Operation The Main Controls
Ready for operation The main controls You can carry out all the settings for the heating circuits centrally on the con trol unit and on the built-in programming unit. If your system is equipped with remote controls, you can also use the remote controls for the settings.
-
Page 5: Overview Of Controls And Indicators
Ready for operation Overview of controls and indicators Heating circuit selector buttons (page 7) Display window Hinged cover of programming unit Normal room temperature (page
Heating programs (page 7) Energy saving mode (page 10) Party mode (page 9) Only on Vitotronic 050, Type HK3W: Heating system on/off switch (page 11) Fuse Operating status indicator (green)
-
Page 6
Ready for operation Overview of controls and indicators (continued) Other display symbols Adjustment of the display window Flashing data (These are not displayed continu contrast Data flashing in the display window ously, but appear according to sys Open the hinged cover on the pro means that new settings can be en tem type and operating status) gramming unit, press d and, at the… -
Page 7: Selecting The Heating Program (Winter, Summer)
Ready for operation Select the heating circuit before every setting and scanning operation With only one heating circuit connected, you can start making all settings straightaway. On heating systems with two or three heating circuits, the corresponding heating circuit must be selected before carrying out each setting and scan ning operation.
-
Page 8
Ready for operation Changing the room temperature In the «Central heating and domestic hot water» heating program, central heat ing takes place with alternating «normal room temperature» and «reduced room temperature» according to the selected time program (see page 12). You can set the required room temperature as follows: To change the «normal room temperature»… -
Page 9
Using the comfort functions Setting the party mode Switch on the party mode when you require central heating and domestic hot water (if a DHW cylinder is installed) for a short time independently of the preset heating and time program. To activate the party mode 1. -
Page 10: Activating The Energy Saving Mode
Using the comfort functions Activating the energy saving mode The energy saving mode is only possible in the «rw» heating program. Switch on the energy saving mode when you require particularly economic central heating for a short time. In the energy saving mode the preset room temperature is automatically lowered.
-
Page 11: Shutting Down The Control Unit/Heating Circuits
Switching on and off Starting up the control unit/heating circuits The initial start-up and matching of the heating circuits to local conditions and the structural characteristics of the building must be carried out by your heating contractor. 1. Switch on the mains voltage, e.g. at the separate fuse or a mains electrical isolator switch.
-
Page 12: Settings Time Programs
Settings Time programs You can select time programs for central heating, domestic hot water (if a DHW cylinder is installed) and the DHW circulation pump (if installed). The DHW circulation pump ensures that hot water is available at the taps when required.
-
Page 13
Settings Time programs (continued) Changing and scanning the time program for central heating 11. Open the hinged cover on the programming unit. 12. Press the heating circuit selector button; the button is lit. 13. A Press A; the «Central If you wish to exit the time program heating time program»… -
Page 14
Settings Time programs (continued) Changing and scanning the time program for central heating (continued) To exit the setting mode at any time 1. A Press A; the display changes to «Exit? Yes». 2. d Press d to confirm; the basic display appears. To scan the time phases Follow the procedure described on page 13, but without using the a… -
Page 15
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump The automatic mode is selected in the time program for domestic hot water and the DHW circulation pump, i.e. domestic hot water heating takes place in parallel with the central heating time program, but starts 30 minutes earlier. -
Page 16
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) 16. a/b Press a/b until one of Please note: the following displays ap If different time phases are set for pears in the display win individual days of the week and dow:… -
Page 17
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) To exit the setting mode at any time 1. B Press B; the display changes to «Exit? Yes». 2. d Press d to confirm;… -
Page 18: Changing The Domestic Hot Water Temperature
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) Domestic hot water heating on a one-off basis outside the programmed time phases 1. Press the heating circuit selector button;…
-
Page 19: Setting The Energy Saving Mode For The Holiday Period
Settings Setting the energy saving mode for the holiday period If you want to set your heating circuit to the minimum energy consumption, e.g. while you are away on holiday, choose the holiday program or the standby mode (see «Selecting the heating program» on page 7). Holiday program Example To protect house plants during…
-
Page 20
Settings Setting the energy saving mode for the holiday period (continued) 1. Open the cover on the program ming unit. 2. H Press H; the «Holiday If you want to erase the holiday program» display appears program during the setting pro in the display window. -
Page 21: Resetting The Time And Date
Other settings Resetting the time and date The time and date are preset in the factory and can be changed manually. There is no need manual resetting in conjunction with a radio clock receiver (accessory). 1. Open the hinged cover on the pro gramming unit.
-
Page 22: Changing The Heating Pattern
Other settings Changing the heating pattern The heating pattern is influenced by the outdoor temperature and the settings of the «shift» and «slope» of the «heating curve». Heating curves represent the relationship between the outdoor temperature and the flow temperature. Put simply: The lower the outdoor temperature, the higher the flow temperature.
-
Page 23
Other settings Changing the heating pattern (continued) Changing the heating pattern by adjusting the heating curve 1. Open the hinged cover on the pro gramming unit. 2. Press the heating circuit selector button; the button is lit. 3. I Press I for «Slope» As a guide, please refer to the Slope table headed «Change heating… -
Page 24
Other settings Changing the heating pattern (continued) Change heating pattern if … Action Example … the accommodation is too cold at Adjust the slope of the cold time of year heating curve upwards by Slope one increment … the accommodation is too warm Adjust the slope of the at cold time of year heating curve downwards… -
Page 25
Scanning Scanning temperatures and operating status information You can scan various current temperatures and operating status information depending on the system components connected and the settings made. H User no. in conjunction with other control units H Holiday program with dates of if entered departure and return H Holiday program active… -
Page 26: Remote Control
Troubleshooting guide Special displays It is not possible to make settings on Example Remote control the control unit, only on the remote «Normal room temperature» on control. the «ts» selector knob can only be set on the remote control. This display flashes when you have Example Without function pressed a button to which no func…
-
Page 27: Diagnosis And Correction
Troubleshooting guide Diagnosis and correction If a fault occurs, it will be indicated in the display window and by the flashing DFault red fault lamp (see page 5). Using the scan facility, you can read off the fault code yourself and inform ºC your heating contractor accordingly.
-
Page 28
Troubleshooting guide Diagnosis and correction (continued) Fault Cause Remedy The heating circuit remains cold Heating system switch «8» on the Switch on control unit turned to OFF Mains voltage is switched off Switch on mains voltage Fuse in the domestic power circuit Inform heating contractor or in the control unit has blown or tripped… -
Page 29: Servicing/Cleaning Instructions And Note On Disposal Of Unwanted Equipment
Servicing instructions/How to save energy Servicing/cleaning instructions and note on disposal of unwanted equipment Servicing Cleaning Note on disposal of unwanted equip Servicing of heating systems is re The equipment can be cleaned with ment quired under current heating system domestic cleaning agents available The unit contains an inbuilt, non-toxic regulations and standards (DIN 4755,…
-
Page 30: Alphabetical Index
Winter operation, 7 Work on the equipment, 2 Factory settings, 4, 5, 6, 7 Fault display, 5, 27 Reduced room temperature (night Viessmann Werke GmbH & Co Fault messages, 27 temperature), 5, 7, 8 D-35107 Allendorf Faults, 27 Remote control, 4, 26…
Viessmann
Каскадные контроллеры Viessmann серии Vitotronic 333 и контроллеры отопительных контуров Vitotronic 050 для установки в шкафы управления. Технический паспорт.
Скачать
Pdf 735.32 Kb
Язык: RU
-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
Operating Instructions
for the system user
Vitotronic 050
Type HK3W and HK3S
Weather-compensated, digital heating circuit control units
VITOTRONIC 050
Vitotronic 050, Type HK3W
Vitotronic 050, Type HK3S
5592 395 GB
4/2001
File in service document ring binder
Related Manuals for Viessmann VIVOTRONIC 050 HK3W
Summary of Contents for Viessmann VIVOTRONIC 050 HK3W
-
Page 1
Operating Instructions for the system user Vitotronic 050 Type HK3W and HK3S Weather-compensated, digital heating circuit control units VITOTRONIC 050 Vitotronic 050, Type HK3W Vitotronic 050, Type HK3S 5592 395 GB 4/2001 File in service document ring binder… -
Page 2: For Your Safety
Introductory information For your safety Please follow these safety instructions closely to avoid the risk of injury to persons and damage to property. If you smell gas Work on the equipment Boiler room conditions H Don’t smoke! Don’t use naked Installation, initial start-up, mainte H Do not use a room in which the air flames or cause sparks (e.g.
-
Page 3: Table Of Contents
Index Page Useful tips Introductory information For your safety ………………..Instructions in brief Ready for operation The main controls…
-
Page 4: Ready For Operation The Main Controls
Ready for operation The main controls You can carry out all the settings for the heating circuits centrally on the con trol unit and on the built-in programming unit. If your system is equipped with remote controls, you can also use the remote controls for the settings.
-
Page 5: Overview Of Controls And Indicators
Ready for operation Overview of controls and indicators Heating circuit selector buttons (page 7) Display window Hinged cover of programming unit Normal room temperature (page
Heating programs (page 7) Energy saving mode (page 10) Party mode (page 9) Only on Vitotronic 050, Type HK3W: Heating system on/off switch (page 11) Fuse Operating status indicator (green)
-
Page 6
Ready for operation Overview of controls and indicators (continued) Other display symbols Adjustment of the display window Flashing data (These are not displayed continu contrast Data flashing in the display window ously, but appear according to sys Open the hinged cover on the pro means that new settings can be en tem type and operating status) gramming unit, press d and, at the… -
Page 7: Selecting The Heating Program (Winter, Summer)
Ready for operation Select the heating circuit before every setting and scanning operation With only one heating circuit connected, you can start making all settings straightaway. On heating systems with two or three heating circuits, the corresponding heating circuit must be selected before carrying out each setting and scan ning operation.
-
Page 8
Ready for operation Changing the room temperature In the «Central heating and domestic hot water» heating program, central heat ing takes place with alternating «normal room temperature» and «reduced room temperature» according to the selected time program (see page 12). You can set the required room temperature as follows: To change the «normal room temperature»… -
Page 9
Using the comfort functions Setting the party mode Switch on the party mode when you require central heating and domestic hot water (if a DHW cylinder is installed) for a short time independently of the preset heating and time program. To activate the party mode 1. -
Page 10: Activating The Energy Saving Mode
Using the comfort functions Activating the energy saving mode The energy saving mode is only possible in the «rw» heating program. Switch on the energy saving mode when you require particularly economic central heating for a short time. In the energy saving mode the preset room temperature is automatically lowered.
-
Page 11: Shutting Down The Control Unit/Heating Circuits
Switching on and off Starting up the control unit/heating circuits The initial start-up and matching of the heating circuits to local conditions and the structural characteristics of the building must be carried out by your heating contractor. 1. Switch on the mains voltage, e.g. at the separate fuse or a mains electrical isolator switch.
-
Page 12: Settings Time Programs
Settings Time programs You can select time programs for central heating, domestic hot water (if a DHW cylinder is installed) and the DHW circulation pump (if installed). The DHW circulation pump ensures that hot water is available at the taps when required.
-
Page 13
Settings Time programs (continued) Changing and scanning the time program for central heating 11. Open the hinged cover on the programming unit. 12. Press the heating circuit selector button; the button is lit. 13. A Press A; the «Central If you wish to exit the time program heating time program»… -
Page 14
Settings Time programs (continued) Changing and scanning the time program for central heating (continued) To exit the setting mode at any time 1. A Press A; the display changes to «Exit? Yes». 2. d Press d to confirm; the basic display appears. To scan the time phases Follow the procedure described on page 13, but without using the a… -
Page 15
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump The automatic mode is selected in the time program for domestic hot water and the DHW circulation pump, i.e. domestic hot water heating takes place in parallel with the central heating time program, but starts 30 minutes earlier. -
Page 16
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) 16. a/b Press a/b until one of Please note: the following displays ap If different time phases are set for pears in the display win individual days of the week and dow:… -
Page 17
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) To exit the setting mode at any time 1. B Press B; the display changes to «Exit? Yes». 2. d Press d to confirm;… -
Page 18: Changing The Domestic Hot Water Temperature
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) Domestic hot water heating on a one-off basis outside the programmed time phases 1. Press the heating circuit selector button;…
-
Page 19: Setting The Energy Saving Mode For The Holiday Period
Settings Setting the energy saving mode for the holiday period If you want to set your heating circuit to the minimum energy consumption, e.g. while you are away on holiday, choose the holiday program or the standby mode (see «Selecting the heating program» on page 7). Holiday program Example To protect house plants during…
-
Page 20
Settings Setting the energy saving mode for the holiday period (continued) 1. Open the cover on the program ming unit. 2. H Press H; the «Holiday If you want to erase the holiday program» display appears program during the setting pro in the display window. -
Page 21: Resetting The Time And Date
Other settings Resetting the time and date The time and date are preset in the factory and can be changed manually. There is no need manual resetting in conjunction with a radio clock receiver (accessory). 1. Open the hinged cover on the pro gramming unit.
-
Page 22: Changing The Heating Pattern
Other settings Changing the heating pattern The heating pattern is influenced by the outdoor temperature and the settings of the «shift» and «slope» of the «heating curve». Heating curves represent the relationship between the outdoor temperature and the flow temperature. Put simply: The lower the outdoor temperature, the higher the flow temperature.
-
Page 23
Other settings Changing the heating pattern (continued) Changing the heating pattern by adjusting the heating curve 1. Open the hinged cover on the pro gramming unit. 2. Press the heating circuit selector button; the button is lit. 3. I Press I for «Slope» As a guide, please refer to the Slope table headed «Change heating… -
Page 24
Other settings Changing the heating pattern (continued) Change heating pattern if … Action Example … the accommodation is too cold at Adjust the slope of the cold time of year heating curve upwards by Slope one increment … the accommodation is too warm Adjust the slope of the at cold time of year heating curve downwards… -
Page 25
Scanning Scanning temperatures and operating status information You can scan various current temperatures and operating status information depending on the system components connected and the settings made. H User no. in conjunction with other control units H Holiday program with dates of if entered departure and return H Holiday program active… -
Page 26: Remote Control
Troubleshooting guide Special displays It is not possible to make settings on Example Remote control the control unit, only on the remote «Normal room temperature» on control. the «ts» selector knob can only be set on the remote control. This display flashes when you have Example Without function pressed a button to which no func…
-
Page 27: Diagnosis And Correction
Troubleshooting guide Diagnosis and correction If a fault occurs, it will be indicated in the display window and by the flashing DFault red fault lamp (see page 5). Using the scan facility, you can read off the fault code yourself and inform ºC your heating contractor accordingly.
-
Page 28
Troubleshooting guide Diagnosis and correction (continued) Fault Cause Remedy The heating circuit remains cold Heating system switch «8» on the Switch on control unit turned to OFF Mains voltage is switched off Switch on mains voltage Fuse in the domestic power circuit Inform heating contractor or in the control unit has blown or tripped… -
Page 29: Servicing/Cleaning Instructions And Note On Disposal Of Unwanted Equipment
Servicing instructions/How to save energy Servicing/cleaning instructions and note on disposal of unwanted equipment Servicing Cleaning Note on disposal of unwanted equip Servicing of heating systems is re The equipment can be cleaned with ment quired under current heating system domestic cleaning agents available The unit contains an inbuilt, non-toxic regulations and standards (DIN 4755,…
-
Page 30: Alphabetical Index
Winter operation, 7 Work on the equipment, 2 Factory settings, 4, 5, 6, 7 Fault display, 5, 27 Reduced room temperature (night Viessmann Werke GmbH & Co Fault messages, 27 temperature), 5, 7, 8 D-35107 Allendorf Faults, 27 Remote control, 4, 26…
Перейти к контенту
-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
Operating Instructions
for the system user
Vitotronic 050
Type HK3W and HK3S
Weather-compensated, digital heating circuit control units
VITOTRONIC 050
Vitotronic 050, Type HK3W
Vitotronic 050, Type HK3S
5592 395 GB
4/2001
File in service document ring binder
Related Manuals for Viessmann VIVOTRONIC 050 HK3W
Summary of Contents for Viessmann VIVOTRONIC 050 HK3W
- Page 1
Operating Instructions for the system user Vitotronic 050 Type HK3W and HK3S Weather-compensated, digital heating circuit control units VITOTRONIC 050 Vitotronic 050, Type HK3W Vitotronic 050, Type HK3S 5592 395 GB 4/2001 File in service document ring binder… -
Page 2: For Your Safety
Introductory information For your safety Please follow these safety instructions closely to avoid the risk of injury to persons and damage to property. If you smell gas Work on the equipment Boiler room conditions H Don’t smoke! Don’t use naked Installation, initial start-up, mainte H Do not use a room in which the air flames or cause sparks (e.g.
-
Page 3: Table Of Contents
Index Page Useful tips Introductory information For your safety ………………..Instructions in brief Ready for operation The main controls…
-
Page 4: Ready For Operation The Main Controls
Ready for operation The main controls You can carry out all the settings for the heating circuits centrally on the con trol unit and on the built-in programming unit. If your system is equipped with remote controls, you can also use the remote controls for the settings.
-
Page 5: Overview Of Controls And Indicators
Ready for operation Overview of controls and indicators Heating circuit selector buttons (page 7) Display window Hinged cover of programming unit Normal room temperature (page Heating programs (page 7) Energy saving mode (page 10) Party mode (page 9) Only on Vitotronic 050, Type HK3W: Heating system on/off switch (page 11) Fuse Operating status indicator (green)
- Page 6
Ready for operation Overview of controls and indicators (continued) Other display symbols Adjustment of the display window Flashing data (These are not displayed continu contrast Data flashing in the display window ously, but appear according to sys Open the hinged cover on the pro means that new settings can be en tem type and operating status) gramming unit, press d and, at the… -
Page 7: Selecting The Heating Program (Winter, Summer)
Ready for operation Select the heating circuit before every setting and scanning operation With only one heating circuit connected, you can start making all settings straightaway. On heating systems with two or three heating circuits, the corresponding heating circuit must be selected before carrying out each setting and scan ning operation.
- Page 8
Ready for operation Changing the room temperature In the «Central heating and domestic hot water» heating program, central heat ing takes place with alternating «normal room temperature» and «reduced room temperature» according to the selected time program (see page 12). You can set the required room temperature as follows: To change the «normal room temperature»… - Page 9
Using the comfort functions Setting the party mode Switch on the party mode when you require central heating and domestic hot water (if a DHW cylinder is installed) for a short time independently of the preset heating and time program. To activate the party mode 1. -
Page 10: Activating The Energy Saving Mode
Using the comfort functions Activating the energy saving mode The energy saving mode is only possible in the «rw» heating program. Switch on the energy saving mode when you require particularly economic central heating for a short time. In the energy saving mode the preset room temperature is automatically lowered.
-
Page 11: Shutting Down The Control Unit/Heating Circuits
Switching on and off Starting up the control unit/heating circuits The initial start-up and matching of the heating circuits to local conditions and the structural characteristics of the building must be carried out by your heating contractor. 1. Switch on the mains voltage, e.g. at the separate fuse or a mains electrical isolator switch.
-
Page 12: Settings Time Programs
Settings Time programs You can select time programs for central heating, domestic hot water (if a DHW cylinder is installed) and the DHW circulation pump (if installed). The DHW circulation pump ensures that hot water is available at the taps when required.
- Page 13
Settings Time programs (continued) Changing and scanning the time program for central heating 11. Open the hinged cover on the programming unit. 12. Press the heating circuit selector button; the button is lit. 13. A Press A; the «Central If you wish to exit the time program heating time program»… - Page 14
Settings Time programs (continued) Changing and scanning the time program for central heating (continued) To exit the setting mode at any time 1. A Press A; the display changes to «Exit? Yes». 2. d Press d to confirm; the basic display appears. To scan the time phases Follow the procedure described on page 13, but without using the a… - Page 15
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump The automatic mode is selected in the time program for domestic hot water and the DHW circulation pump, i.e. domestic hot water heating takes place in parallel with the central heating time program, but starts 30 minutes earlier. - Page 16
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) 16. a/b Press a/b until one of Please note: the following displays ap If different time phases are set for pears in the display win individual days of the week and dow:… - Page 17
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) To exit the setting mode at any time 1. B Press B; the display changes to «Exit? Yes». 2. d Press d to confirm;… -
Page 18: Changing The Domestic Hot Water Temperature
Settings Time programs (continued) Changing and scanning the time program for domestic hot water heating and the DHW circulation pump (continued) Domestic hot water heating on a one-off basis outside the programmed time phases 1. Press the heating circuit selector button;…
-
Page 19: Setting The Energy Saving Mode For The Holiday Period
Settings Setting the energy saving mode for the holiday period If you want to set your heating circuit to the minimum energy consumption, e.g. while you are away on holiday, choose the holiday program or the standby mode (see «Selecting the heating program» on page 7). Holiday program Example To protect house plants during…
- Page 20
Settings Setting the energy saving mode for the holiday period (continued) 1. Open the cover on the program ming unit. 2. H Press H; the «Holiday If you want to erase the holiday program» display appears program during the setting pro in the display window. -
Page 21: Resetting The Time And Date
Other settings Resetting the time and date The time and date are preset in the factory and can be changed manually. There is no need manual resetting in conjunction with a radio clock receiver (accessory). 1. Open the hinged cover on the pro gramming unit.
-
Page 22: Changing The Heating Pattern
Other settings Changing the heating pattern The heating pattern is influenced by the outdoor temperature and the settings of the «shift» and «slope» of the «heating curve». Heating curves represent the relationship between the outdoor temperature and the flow temperature. Put simply: The lower the outdoor temperature, the higher the flow temperature.
- Page 23
Other settings Changing the heating pattern (continued) Changing the heating pattern by adjusting the heating curve 1. Open the hinged cover on the pro gramming unit. 2. Press the heating circuit selector button; the button is lit. 3. I Press I for «Slope» As a guide, please refer to the Slope table headed «Change heating… - Page 24
Other settings Changing the heating pattern (continued) Change heating pattern if … Action Example … the accommodation is too cold at Adjust the slope of the cold time of year heating curve upwards by Slope one increment … the accommodation is too warm Adjust the slope of the at cold time of year heating curve downwards… - Page 25
Scanning Scanning temperatures and operating status information You can scan various current temperatures and operating status information depending on the system components connected and the settings made. H User no. in conjunction with other control units H Holiday program with dates of if entered departure and return H Holiday program active… -
Page 26: Remote Control
Troubleshooting guide Special displays It is not possible to make settings on Example Remote control the control unit, only on the remote «Normal room temperature» on control. the «ts» selector knob can only be set on the remote control. This display flashes when you have Example Without function pressed a button to which no func…
-
Page 27: Diagnosis And Correction
Troubleshooting guide Diagnosis and correction If a fault occurs, it will be indicated in the display window and by the flashing DFault red fault lamp (see page 5). Using the scan facility, you can read off the fault code yourself and inform ºC your heating contractor accordingly.
- Page 28
Troubleshooting guide Diagnosis and correction (continued) Fault Cause Remedy The heating circuit remains cold Heating system switch «8» on the Switch on control unit turned to OFF Mains voltage is switched off Switch on mains voltage Fuse in the domestic power circuit Inform heating contractor or in the control unit has blown or tripped… -
Page 29: Servicing/Cleaning Instructions And Note On Disposal Of Unwanted Equipment
Servicing instructions/How to save energy Servicing/cleaning instructions and note on disposal of unwanted equipment Servicing Cleaning Note on disposal of unwanted equip Servicing of heating systems is re The equipment can be cleaned with ment quired under current heating system domestic cleaning agents available The unit contains an inbuilt, non-toxic regulations and standards (DIN 4755,…
-
Page 30: Alphabetical Index
Winter operation, 7 Work on the equipment, 2 Factory settings, 4, 5, 6, 7 Fault display, 5, 27 Reduced room temperature (night Viessmann Werke GmbH & Co Fault messages, 27 temperature), 5, 7, 8 D-35107 Allendorf Faults, 27 Remote control, 4, 26…
Viessmann
Каскадные контроллеры Viessmann серии Vitotronic 333 и контроллеры отопительных контуров Vitotronic 050 для установки в шкафы управления. Технический паспорт.
Скачать
Pdf 735.32 Kb
Язык: RU
Specifications:
|
Accompanying Data:
Viessmann VIVOTRONIC 050 HK3W Control Unit PDF Operating Instructions Manual (Updated: Friday 24th of February 2023 09:54:23 PM)
Rating: 4.2 (rated by 59 users)
Compatible devices: 5547, EM-EA1 extension, BCU, VITOCAL 150-A, SDIO, 5556, EM-M1, Vivotronic 050 HK1S.
Recommended Documentation:
Viessmann VIVOTRONIC 050 HK3W: Text of Operating Instructions Manual
(Ocr-Read Version Summary of Contents, UPD: 24 February 2023)
-
23, �…
-
7, …
-
15, �…
-
22, �…
-
12, �…
-
17, �…
-
14, …
-
26, …
-
11, �…
-
8, �…
-
28, 8 �…
-
20, �…
-
6, …
-
18, …
-
13, �…
Viessmann VIVOTRONIC 050 HK3W: Recommended Instructions
VSX-9300TX, MR355, HDP 5, i-Go, DELTA 28-984, T620-8
-
Warning: Read the installation instructions thoroughly before installing orservicing this equipment. Improper installation, adjustment, service or maintenancecan cause property damage, injury or death.POTTORFF®5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.comInformation is subject to change without notice or obligation.NOTE: Dimensions in parentheses ( ) are millimeter …
TICD-50 Series 3
-
MB LAN6 720 647 836-00.1O[cs] Návod k instalaci 2[de] Installationsanleitung 6[en] Installation instruction 10[et] Paigaldusjuhend 14[fl] Installatiehandleiding 18[fr] Notice d’installation 22[hr] Upute za instalaciju 26[it] Istruzioni d’installazione 30[lt] Montavimo instrukcija 34[lv] Uzstādīšanas instrukcija 38[pl] Instrukcja instalacji 42[sk] Návod na in …
MB LAN 68
-
Pos: 2 /Dokumentation al lgemein/Einband/Ei nband Handbuch — Fr ontseite 2017 — mit DocVariab len (Standard) @ 28mod_148 6477502910_0.doc x @ 405388 @ @ 1 Manual WAGO-I/O-SYSTEM 750 750-461(/xxx-xxx) 2AI Pt100/RTD 2-Channel Analog Input for Resistance Sensors Version 1.4.1 Pos: 3 /Alle Serien (Al lgemeine Module)/Rec htliches, Allgemeines/ Impressum für Standar dhandbücher — a …
750-461 64
-
CA295Einbauanleitung Installation instructions Notice de montage InstallatiehandleidingIstruzioni di montaggioInstrukcja montażuAnleitung zum späteren Gebrauch aufbewahren!Keep instructions for later use!Conserver la notice pour usage ultérieur!Handleiding bewaren voor later gebruik!Conservare le istruzioni per uso successivo!Zachowa instrukcj do pózniejszego wykorzystania!SystemtrennerB …
CA295 16
-
17” TFT LCD Module USER MANUAL Preliminary 45S17 Information may change without notice. This document provides technical information for the user. Videology reserves the right to modify the information in this document as necessary. The customer should make sure that they have the most recent manual version. Videology holds no responsibility for any …
45S17 12
-
IMPORTANT DOCUMENTS ENCLOSEDCAUTION:To reduce the risk of injury due to hot waterburns, make sure the enclosed labels areapplied where specied on the label.DOCUMENTOS IMPORTANTES INCLUIDOSAVISO:Para reducir el riesgo de lesión porquemaduras de agua caliente , asegúrese quelas etiquetas incluidas se han aplicado dondese ha especicado en la etiqueta.DOCUMENTS IMPORTANTS À L’INTÉRIEURMIS …
MultiChoice 13 Series 38
-
Publication Number QS007SSW07 …
SSW-07 11
-
DOC023.98.90513RTC multi-channel module11/2018, Edition 5User ManualBedienungsanleitungManual del usuarioManuel de l’utilisateurManuale utenteManual do utilizadorGebruikershandleidingBruksanvisningBrugervejledningInstrukcja obsługiNávod k použitíРъководство за потребителяFelhasználói kézikönyvNavodila za uporaboManual de utilizareKullanıcı KılavuzuNávod …
RTC 336
-
Revision 2.1Bedienungs- und MontageanleitungOperating and installation instructionsAnvändnings- och monteringsinstruktionPro-nderTelemetriemodul zur Flottenüberwachungund SteuerungTelemetry module for eet monitoring and controlTelemetrimodul för övervakning och styrning av fordon …
Pro-finder 48
Additional Information:
Operating Impressions, Questions and Answers:
VITOTRONIC 050
Operating Instructions
for use by the system user
Vitotronic 050, Model HK1M Digital indoor/outdoor heating circuit control unit
Certified as a component part
of Viessmann boilers only
Pl ea se fil e in Se rv ic e B in de r
5285 968 v1.0 11/2005
2
Safety instructions
Safety, Installation and Warranty requirements
Please ensure that this manual is read and understood before commencing installation. Failure to comply with the issues listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
Licensed professional heating contractor The installation, adjustment, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.
Please see section entitled Important Regulatory and Installation Requirements.
Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature, please see section entitled Important Regulatory and Installation Requirements.
Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders warranty null and void.
Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
Safety Terminology
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include WARNING, CAUTION, and IMPORTANT. See below.
Helpful hints for installation, operation or maintenance which pertain to the product.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial product / property damage.
DANGER
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product / property damage.
WARNING
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage.
CAUTION
IMPORTANT
3
Index
Index
Introductory information Initial start-up 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control unit factory default settings 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Where to find the controls Summary of controls and indicators 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functions 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display window symbols 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start-up/shutdown Control unit start-up 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control unit shutdown 6.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the heating circuit 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shutting down the heating circuit 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Room temperature Setting a heating circuit time program 7.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting a normal room temperature 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting a reduced room temperature 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting switching times (timer program) 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Further settings Time and date 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chnaging heating characteristics 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing slope and level 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning options Scanning temperatures 12.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning time programs 12.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What to do if … … rooms are too cold? 13.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
… rooms are too hot? 14.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
… fault symbol U flashes in the display? 14.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning fault display 14.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repairs Cleaning 15.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection and maintenance 15.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Energy saving tips 15.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keyword index 16.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
4
Introductory information
Initial start-up
The initial start-up and matching of the control unit to local conditions and the structural characteristics of the building must be carried out by your heating contractor.
Control unit factory default settings
The control unit is preset at the factory for standard operation: Between 06:00 and 22:00 h, space heating operates at normal room temperature. Between 22:00 and 06:00 h, space heating with reduced room temperature (set to 3 C / 37 F, freeze-up protection).
Weekday and time (CET) were set up in the factory. Daylight saving time is automatic.
You may change the factory default settings in accordance with personal requirements.
Please note: All data is saved in case of power failure.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
5
Where to find the controls
Summary of controls and indicators
You can change all settings for your heating circuit centrally at the control unit.
You may also make some adjustments on the remote control unit, if your system is equipped with a Vitotrol 200 remote control (see separate operating instructions).
Functions
A Normal room temperature (page 7) B Reduced room temperature (page 7) C Space heating (page 6) D Only for service E Standby mode (page 6) F Confirmation G Power ON/OFF switch (page 6) H Basic settings K Information (page 12)
L Value setting M Heating curve level (page 9) N Time/Date (page 9) O Heating curve slope (page 9) P Time program (page 7)
Basic setting D
All modified values for the heating circuit are returned to their factory default settings.
Display window symbols
| Points to the current day of the week (1 to 7) s For space heating with normal room temperature m For space heating with reduced room temperature C Unit of temperature value U Fault indication h Unit of time u Time program
Time cycles 1 to 4 Start of time cycle End of time cycle r Space heating active rpHeating circuit pump operates
These symbols are not permanently displayed, but appear subject to the system version and the operating state. Flashing displays indicate that modifications can be made.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
20
10 30
C 1234567
+ OK
HKLMNOP
A
B
E F
G
C D
6
Start-up/shutdown
Control unit start-up
1. Turn power supply ON. Turn on breaker or main disconnect supplying 120 VAC to unit.
2. Push ON/OFF button to turn power ON. After a short time, the supply temperature is displayed. Your control unit and, if installed, your remote control unit are now ready to operate.
Control unit shutdown
If you intend shutting down your control unit for a while, e.g. during a summer holiday, set the heating circuits to standby (see page 6).
Please note: The heating circuit pump starts automatically every 24 hours for a short time to prevent pump damage.
If you do not want to use the heating circuit, you should shut down the control unit.
1. Push ON/OFF button to turn power OFF.
2. Isolate the system from the power supply. Turn off breaker or main disconnect supplying 120 VAC to unit. Please note that the system is no longer freeze-up protected.
Please note: All settings remain intact.
Starting the heating circuit
Press r ; Space heating
Space heating with normal or reduced room temperature (freeze-up protection) according to the programmed times Basic setting: from 06:00 to 22:00 h normal room temperature, otherwise reduced room temperature Heating circuit freeze-up protection active
Shutting down the heating circuit
Press ; Standby mode
No space heating Heating circuit freeze-up protection active
Please note: The heating circuit pump starts automatically every 24 hours for a short time to prevent pump damage.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
7
Room temperature
Setting heating circuit time program
Observe the following 3 points if you want to activate space heating.
1.Heating r must be selected for the heating circuit.
2.Normal room temperature (for day) ts and reduced room temperature (for night) tm can be selected for the heating circuit (see below).
3.When your heating circuit operates with normal or reduced room temperature depends on the programmed times (four possible time cycles) for the respective day.
If no time cycles are selected, space heating will be active for the whole day at reduced room temperature. If one or more time cycles are selected, space heating will be active for those times with normal room temperature. For changing programmed times, see below.
Setting a normal room temperature
Set the desired temperature for the normal room temperature with rotary selector ts.
Setting a reduced room temperature
Press the following keys:
1. tm for reduced room temperature; the currently set temperature will flash.
2. / for the desired value.
3. as confirmation; the temperature no longer flashes and is now saved.
Setting switching times (timer program)
4 time cycles: For space heating, up to four changes between normal and reduced room temperature can be programmed. At the factory, time cycle 1 from 06:00 to 22:00 h is set for every weekday i.e. during that time, all rooms are heated to the normal room temperature.
You can select identical time programs for all weekdays or individual programs for each weekday.
When setting time programs please note that your heating system requires some time to heat the rooms to the desired temperature.
For time programming steps, see page 8. For a sequence of steps to delete a time cycle, see page 8.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
C
7654321
C
7654321
8
Room temperature
Setting a permanent room temperature (cont.)
Press the following keys:
1.ur for time program.
Please note: If you want to terminate the time programming prematurely, press key ur again.
2. / to below all weekdays (1 to 7) arrows flash if you want to set the same time cycles for every weekday
or one arrow flashes below the desired weekday if you want to set alternative time cycles for the displayed weekday.
Please note: If different time cycles are set for individual weekdays, and if you want to set up identical time cycles for all weekdays, press when the arrows flash below every weekday. All time cycles are returned to their original condition.
3. for confirmation; time cycle 1 will then be displayed.
Press if you want to skip a time cycle.
4. for confirmation; the time cycle start point then flashes.
5. / for time cycle start point.
6. for confirmation; the time cycle end point then flashes.
7. / for time cycle end point.
8 for confirmation; the next time cycle is then displayed.
9. Proceed for the setting up of the start and end of time cycles 2 to 4 as described under steps 5 to 8.
Press the following keys if you want to delete a time cycle:
1.ur for time program.
2. until the time cycle end point to be deleted flashes.
3. until — -:- — for the end time point is displayed.
4. for confirmation, until the supply temperature is displayed.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
7654321
7654321
7654321
7654321
7654321
9
Further settings
Time and date
Date and time are factory-set and may be changed manually.
Press the following keys:
1.u for time.
2. / for desired time.
3. as confirmation; the year flashes.
4. / for the desired year.
5. as confirmation; the month flashes.
6. / for the desired month.
7. as confirmation; the day flashes.
8. / for the desired day.
9. for confirmation.
Changing heating characteristics
You can alter the heating characteristics by changing the slope and level of the heating curve. For more information regarding the heating curve, see page 11. Please observe the modified heating characteristics over several days (if possible, await a major change in the weather), before making further adjustments. Make short-term adjustments of the room temperature using rotary selector ts or key tm (see page 7).
Changing slope and level
For assistance, use table on changing heating characteristics on page 10. Press the following keys:
1.n for slope
or
N for shift.
2. / for the desired value.
3. for confirmation. Please note: Setting the slope or shift of the heating curve too high or too low will not result in damage to your heating circuit.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
7654321
7654321
7654321
7654321
7654321 7654321
10
Further settings
Changing heating characteristics (cont.)
Changing heating characteristics if … Remedy Example
… living accommodation is too cold during heating season
Adjust heating curve slope to next higher value (e.g. 1.5)
7654321
… living accommodation is too hot during heating season
Adjust heating curve slope to next lower value (e.g. 1.3)
7654321
… living accommodation is too cold during transitional periods (spring/autumn)
Adjust heating curve shift to a higher value (e.g. +3 C / +5 F )
7654321
… living accommodation is too hot during transitional periods (spring/autumn) and during heating season
Adjust heating curve shift to a lower value (e.g. 3 C / 5 F)
7654321
… living accommodation is too cold during transitional periods (spring/autumn), but warm enough during heating season
Adjust heating curve slope to next lower value (e.g. 1.3)
7654321
and shift to a higher value (e.g. +3 C/ +5 F)
7654321
… living accommodation is too hot during transitional periods (spring and autumn), but warm enough during heating season
Adjust heating curve slope to next higher value (e.g. 1.5)
7654321
and shift to a lower value (e.g. 3 C / 5 F)
7654321
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
11
Further settings
Changing heating characteristics (cont.)
Heating curves represent the relationship between the outside temperature and the flow temperature. To put it simply: the lower the outside temperature, the higher the supply temperature. The illustrated heating curves apply subject to the following settings:
Shift = 0 Different level settings shift the curve parallel in a vertical direction. Normal room temperature = approx. 20 C / 68 F.
In the factory, the following settings are made: slope = 1.4, shift = 0.
Generally, the heating curve lies in range A for underfloor heating systems in range B for low temperature heating systems in range C for heating systems with boiler water temperatures above 75 C / 167 F
Examples Well insulated home in sheltered position (with radiator heating system): Slope = 1.2 Home in exposed position or with an older heating system (with radiator heating system): Slope = 1.6
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
B
A
C
12
Scanning options
Scanning temperatures
Subject to connected components and settings made, you can scan current temperatures and operating conditions.
0 01 User no., in conjunction with additional control units 1 18 C Outside temperature 6 35 C Return temperature, if a sensor is installed 7 39 C Supply temperature d 21 C Room temperature, if a Vitotrol remote control is installed 16 : 35 u Time 20 03 Year
: 12 Month 23 : Day
Press the following keys:
1. for scanning.
2. / for further scanning of the list.
3. for ending the scan.
Scanning time program
Proceed as described on page 8, but without pressing or .
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
7654321
C
13
What to do if …
… rooms are too cold?
Cause Remedy
Heating circuit is switched OFF Push the ON/OFF button to turn ON. (see page 6) Switch ON the poewr disconnect, if installed (outside the boiler room) Check fuse/breaker inside electrical panel and notify your local heating contractor
Control unit incorrectly adjusted Check settings and correct if required: Heating circuit must be switched ON (see page 6) Room temperature (see page 7) Time (see page 9) Heating characteristics (see page 9)
Control unit fault: Fault symbol U flashes in display
Scan the type of fault (see page 14) and notify your local heating contractor
Mixer motor faulty Unlock motor lever A and operate mixer leverB manually. Notify your local heating contractor.
A
B
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
14
What to do if …
… rooms are too hot?
Cause Remedy
Control unit incorrectly adjusted Check settings and correct if required: Room temperature (see page 7) Time (see page 9) Heating characteristics (see page 9)
Control unit fault or outside temperature sensor faulty: Fault symbol U flashes in display
Scan the type of fault (see below) and notify your local heating contractor
Mixer motor faulty Unlock motor lever A and operate mixer leverB manually. Notify your local heating contractor.
A
B
… fault symbol U flashes in the display?
Cause Remedy
Control unit fault Scan for faults (see below) and notify your local heating contractor
Scanning fault display
If your heating system has developed a fault, it will be displayed and indicated by flashing fault symbol U. You can read off the fault code on the display by scanning, then notify your local heating contractor accordingly. This allows the heating contractor to prepare better for the service call and may save additional travelling costs.
Press the following keys:
1. / for troubleshooting.
Example
In this case, notify your local heating contractor of the numbers 1, 1 and 8.
2. for acknowledgement.
Please note: If the fault has not been rectified, the fault message will again be displayed at 07:00 h on the following day.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
7654321
15
Repairs / Energy saving tips
Cleaning
All devices may be cleaned with a commercially available domestic cleaning agent (non-scouring).
Inspection and maintenance
Regular maintenance ensures trouble-free, energy-efficient and environmentally responsible heating operation. We strongly advise you to arrange an inspection and maintenance contract with your local heating contractor.
Energy saving tips
Not only will you benefit from the advantages of a modern heating system, but you can also save energy by the way you operate your system. For this, the following measures will help you:
Correct ventilation Briefly open windows A fully, and at the same time close thermostatic radiator valvesB. Do not overheat, endeavour to achieve a room temperature of 20 C; every degree of room temperature reduction saves up to 6% of your heating bills. Close roller shutters (where installed) at dusk. Set thermostatic radiator valves B correctly. Do not cover radiators C or thermostatic radiator valves B. Make full use of the setting options offered by control unit D, e.g. normal room temperature alternating with reduced room temperature.
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
A C
B
D
16
Keyword index
Keyword index
A Actual temperature scanning 12.. . . . . . . . .
Applicability NO TAG.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B Basic settings 4, 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C Space heating 4, 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning tips 15.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controls 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control unit shutdown 6.. . . . . . . . . . . . . . . . . . . . . . . .
Control unit start-up 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D Danger 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Date changing 5, 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Day temperature 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Default settings of control unit 4. . . . . . . .
E Errors (faults) 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F Fault display 14.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault message acknowledgement 14.
Fault message scanning 14.. . . . . . . . . . . . . . . . . . .
Fault messages (What to do if …) 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Freeze-up protection 4, 6. . . . . . . . . . . . . . . . . . . . . . . .
H Heating characteristics 9. . . . . . . . . . . . . . . . . . . . . . . .
Heating circuit shutdown 6.. . . . . . . . . . . . . . . . . .
Heating circuit start-up 6. . . . . . . . . . . . . . . . . . . . . . . .
Heating curve 5, 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating energy saving 15.. . . . . . . . . . . . . . . . . . . . . .
Heating times, changing 7. . . . . . . . . . . . . . . . . . . . .
I Individual time programs 7.. . . . . . . . . . . . . . . . . . . .
Initial start-up 4, 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection 15.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L Level of heating curve, changing 9. . . .
M Maintenance 15.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance contract 15. . . . . . . . . . . . . . . . . . . . . . . .
N Night temperature 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
O ON/OFF switch 4, 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P Programming unit 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program setting 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R Reduced room temperature (night temperature) 4, 5, 7. . . . . . . . . . . . . . . . . . . .
Remote control 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Renewed start-up 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repairs 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Room temperature changing 7. . . . . . . . . . . . .
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
17
Keyword index
Keyword index (cont.)
S Safety instructions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Saving energy 15.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning temperatures and operating conditions 12.. . . . . . . . . . . . . . . . . . . . . . . . . .
Sensor error message 14.. . . . . . . . . . . . . . . . . . . . . . .
Set heating times, changing 7. . . . . . . . . . . . .
Shutting down 6.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Slope of heating curve, changing 9. . .
Standard mode (basic setting) 4. . . . . . . . .
Normal room temperature (day temperature) 4, 5, 7. . . . . . . . . . . . . . . . . . . . . . .
Standby mode 6.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Summer mode 6.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching OFF equipment 6. . . . . . . . . . . . . . . . . .
Switching ON equipment 6. . . . . . . . . . . . . . . . . . . .
Switching times 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols in display 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
T Temperature scanning 12.. . . . . . . . . . . . . . . . . . . . . .
Temperature setting 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time changing 5, 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time cycle deletion 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time prog. for space heating 4, 7. . . . . . . . . . . .
Time program scanning 12.. . . . . . . . . . . . . . . . . . . .
Troubleshooting 13.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
W Weekday 4.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What to do if … 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Where to find the controls 5. . . . . . . . . . . . . . . . .
Winter mode 6.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
18
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
19
5 2 8 5 9 6 8
V 1 .0
1 1 /2 0 0 5
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca mail@viessmann.ca
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com mail@viessmann-us.com
20
Quick Reference
C F
-40 -40 -35 -31 -25 -13 -20 -4 -18 0 -16 +3 -14 +7 -12 +10 -10 +14 -9 +16 -8 +18 -7 +19 -6 +21 -5 +23 -4 +25 -3 +27 -2 +28 -1 +30 0 +32 +1 +34 +2 +36 +3 +37 +4 +39 +5 +41 +6 +43 +7 +45 +8 +46 +9 +48 +10 +50 +12 +54 +14 +57 +16 +61 +18 +64 +20 +68 +25 +77 +30 +86 +35 +95 +40 +104 +50 +122 +60 +140 +70 +158 +80 +176 +90 +194 +100 +212 +110 +230 T
ec hn
ic al
in fo rm
at io
Alubox
Alubox X-treme
Alucon
Antifrogen
Aquacarbon
Aquahome
Atola
CeraCell
Condensola
Dekamatik
Divicon
EOMIX
EON
Eurola
Fauch
HoriCell
IS1500
Kospel EKCO
Kospel VSWK
Litola
Litola-CL
MatriX
Paromat
Pendola
Rondomat
RudoCell
SpiroTech
ST250
SW250
SW250LD
Trimatik
Turbomat
Ultrabox
Unit-P
Unomatik
VertiCell
VICare
Vitoair
Vitobloc 200
Vitocal
Vitocal 100-S/111-S
Vitocal 200-G
Vitocal 222-G
Vitocal 242-G
Vitocal 300
Vitocal 300-G
Vitocal 300-G Pro
Vitocal 300-G/350-G
Vitocal 300-G/W Pro
Vitocal 300-W Pro
Vitocal 333-G
Vitocal 343-G
Vitocal 350-G
Vitocal 350-G Pro
Vitocell
Vitocell 050-E
Vitocell 100
Vitocell 100-B
Vitocell 100-B/100-W
Vitocell 100-E
Vitocell 100-H
Vitocell 100-L
Vitocell 100-U
Vitocell 100-V
Vitocell 100-V/-W
Vitocell 100-W
Vitocell 100-W 100 л
Vitocell 100-W 80 л
Vitocell 120-E
Vitocell 140-E
Vitocell 160-E
Vitocell 300-B
Vitocell 300-H
Vitocell 300-V
Vitocell 300-V/-W
Vitocell 300-V/300-W
Vitocell 300-W
Vitocell 333
Vitocell 333/353
Vitocell 340-M
Vitocell 340?M/360?M
Vitocell 353
Vitocell 360-M
Vitocell-W 100
Vitocell-W 300
Vitoclima 230-S
Vitocom 100
Vitocom 200
Vitocom 300
Vitoconnect
Vitocrossal
Vitocrossal 100
Vitocrossal 200
Vitocrossal 300
Vitodens
Vitodens 050-W
Vitodens 100-W
Vitodens 111-F
Vitodens 111-W
Vitodens 141-F
Vitodens 200-W
Vitodens 200-W/300-W/333-W
Vitodens 200?W
Vitodens 222-F
Vitodens 222-W
Vitodens 222/333
Vitodens 242-F
Vitodens 300-W
Vitodens 333
Vitodens 333-F
Vitoflame 100
Vitoflame 200
Vitoflame 300
Vitogas
Vitogas 050
Vitogas 100
Vitogas 100-F
Vitogate 200
Vitogate 300
Vitola
Vitola 100
Vitola 200
Vitola-biferral
Vitola-comferral
Vitoladens
Vitoladens 300-C
Vitoladens 300-T
Vitoladens 300-W
Vitolig 150
Vitoligno 100-S
Vitomax
Vitomax 100
Vitomax 100-HS
Vitomax 100-LW
Vitomax 200
Vitomax 200-HS
Vitomax 200-HW
Vitomax 200-LW
Vitomax 300
Vitomax 300-HS
Vitomax 300-HW
Vitomax 300-LT
Vitomax 300-LW
Vitomax HS
Vitomax HW
Vitomax LCB
Vitomax LW
Vitomax-HS
Vitopend
Vitopend 050-W
Vitopend 100
Vitopend 100-W
Vitopend 100-W/200-W
Vitopend 111-W
Vitopend 200-W
Vitopend 222-W
Vitoplex
Vitoplex 100
Vitoplex 100-LS
Vitoplex 200
Vitoplex 300
Vitoplex 300 895-1750 кВт
Vitoplex/Vitorond/Vitomax
Vitoplus
Vitoradial
Vitoradial 300-T
Vitorond
Vitorond 100
Vitorond 111
Vitorond 200
Vitorondens 200-T
Vitorondens 222-F
Vitoset
Vitosoft 300
Vitosol
Vitosol 100
Vitosol 100-F
Vitosol 100-F/-FM
Vitosol 100-FM
Vitosol 141-FM
Vitosol 200
Vitosol 200-F
Vitosol 200-FM
Vitosol 200-T
Vitosol 200-TM
Vitosol 300
Vitosol 300-T
Vitosol 300-TM
Vitosolar 300-F
Vitosolic 100
Vitosolic 200
Vitotherm
Vitotrans
Vitotrans 100
Vitotrans 100-LW
Vitotrans 200
Vitotrans 200-LW
Vitotrans 222
Vitotrans 300/333
Vitotrans 300/333 1860-6600 кВт
Vitotrans 300/333 575-2000 кВт
Vitotrans 353
Vitotrol 100
Vitotrol 200-A
Vitotrol 200-E
Vitotrol 300
Vitotrol 300-A
Vitotrol 300-B
Vitotrol 300-E
Vitotron 100
Vitotronic
Vitotronic 050
Vitotronic 100
Vitotronic 100 HC1B
Vitotronic 100/200/300
Vitotronic 100/333
Vitotronic 200
Vitotronic 200 HO1B
Vitotronic 200 WPR3. Контроллер теплового насоса Vitocal
Vitotronic 200-H
Vitotronic 200. Контроллер теплового насоса Vitocal
Vitotronic 300
Vitotronic 300-K
Vitotronic 333
Vitotronic SPS
Vitovent 050-D
Vitovent 100-D
Vitovent 200-C
Vitovent 300-F
Vitovent 300-W
Vitplex
Vitоdens 200-W
Wallcon X-treme
WBS Ligna 050
ZONT H-2000/2000+
Адаптер электрических подключений
Блок управления приводом смесителя OpenTherm
Горелки
Горелки Bluetwin
Горелки Bluetwin/Unit
Датчик СО2 Vitovent 300-W
Дополнительный комплект/манометр
Комнатный термостат ST-BSOP/ST-PSOP
Контроллер KR
Контроллер SR
Контроллер Vitotrans 353
Модуль управления гелиоустановкой SDIO/SM1A
Насосные группы PAW
Нормативные показатели качества воды
Панель управления системой вентиляции
Платформа для техобслуживания котла
Примеры схем отопительных установок. Часть I
Примеры схем отопительных установок. Часть II
Примеры схем отопительных установок. Часть III
Примеры схем установок Vitosolic 100
Принадлежности
Принадлежности Vitotronic
Регулятор температуры помещения OpenTherm
Системы воздухораспределения Vitovent 300-W
Сифон Aquahome
Смесители отопительных контуров
Термическая станция водоподготовки Деаэратор
Универсальные радиаторы
Шкаф управления Vitocontrol
Шлюз WAGO MB/TCP-MB/RTU
Штиль ИнСтаб IS550
Штиль ИнСтаб SW250SL
Экономические показатели котельных установок